A COMPARISON OF CONVENTIONAL AND SPF ROOFING SYSTEMS
Sam Cohen
Project Management Supervisor
Engineering Design Services
Physical Plant Department
Texas A&M University
In 1974, dissatisfied with performance of traditional
tar and gravel built-up roofing (BUR) systems, the Physical Plant Department
began looking for viable roofing alternatives. The BUR roofs were constantly
leaking and because of the nature of BUR, leak detection was virtually impossible.
As the Physical Plant Department began soliciting information from various roofing
sources and checking references, sprayed polyurethane foam (SPF) roofs exhibited
advantages that seemed to fit the criteria of the University.
The Physical Plant Department found the following :
-
Seams are one of the major sources of leaks in roof systems and SPF roofs are totally seamless.
-
Water does not travel laterally in SPF roofs as it can in BUR or single-ply roofs. A leaks in the top membrane of a BUR or single-ply roof will create the spreading of water, saturating the insulation and causing multiple interior leaks. With SPF, even if a hole is punched through the entire two-inch membrane, water movement will be restricted to the hole. In most cases repairs can be made with a tube of caulk.
-
Because the SPF roof is lightweight, permeable and fully adhered, normally an old roof does not need to be removed in order to apply a new one. If underlying areas of saturated insulation are found, minimal tear-off may be required.
-
The SPF roofing is less disruptive to students and faculty since tear-off is minimal. Also, projects are accomplished faster because the application is quieter, quicker and requires far less laborers.
-
Roof mounted units, penetrations, curbs, and parapets can receive a seamless monolithic application because SPF is spray applied. BUR and single-ply roofs require flashing materials with sealants which frequently result in leaks.
In 1974-75, convinced the proceeding advantages warranted taking a look at this
relatively new roofing system, the Physical Plant Department issued contracts
for the reroofing of several buildings. One of the earliest roofs done with
this system was Davis-Gary dorm. After seventeen years this roof has not leaked
and requires minimal maintenance. Between 1975 and 1977 the Physical Plant Department
and TAMU Systems Facilities Planning and Construction (FPC) communicated back
and forth concerning the monitoring of these roof installations. New BUR roofs
were providing the University with service life of less than five years and
many of the BURs were leaking from the onset. In 1977 the Physical Plant Department
foamed over a BUR application that was less than four years old. After monitoring
the SPF installations, FPC was also convinced and since 1977 all new roof applications
have used SPF roofs. FPC received numerous complaints stemming from this decision.
Few roofing contractors had the financial ability to mobilize spraying foam.
Fewer still had the caliber of crews that chemically formulate foam in the field.
Though this eliminated potential bidders, it in effect greatly elevated the
caliber of roofing contractor performing work at Texas A&M.
Many outside architects working at the University were unfamiliar with the system
and some of these had a reluctance to learn anything new, but the Physical Plant
and FPC were adamant. As time went by, architects and general contractors learned
the many advantages of the system. This caused proliferation of the SPF Roof
systems in surrounding school districts and universities. Today over 7 million
square feet of SPF roofing has been applied throughout the A&M system. With
very few exceptions, these roofs are holding up extremely well. In fact, it
is extremely rare that one of these roofs leaks at all. Blister defects, which
occasionally occur, do not create leak problems. Most leak problems at our campus
occur on the few buildings that still have BUR on them.
In 1985 the Physical Plant Department found another advantage in using SPF roofing
systems. For a number of years, Mr. Gerald Scott, P.E. was in charge of roofing
and energy conservation within the Physical Plant Department. Vendors of the
SPF system always championed the energy saving characteristics of the system.
We realized polyurethane was a most effective insulation, but our main concern
had always been to prevent roof leaks. Mr. Scott monitored energy savings on
27 different buildings that had received SPF roofs from 1980 to 1984. The results
were astounding. TAMU was able to recover the complete cost of the roof application
through energy savings in an average of four and one-half years. Quoted here
is Mr. Scott's conclusion, which is still shared by today's Physical Plant Department:
From the time of construction and throughout the life of the roof, built-up
roofs were major maintenance and repair items. The experience that the Texas
A&M University Physical Plant gained since 1974, when they began, indicates
that no major problem, and very few minor ones exist in the polyurethane roof
systems.
As a result of this experience, all new construction includes the foamed polyurethane
roof system. To date some 16 new facilities have this roof system totaling nearly
one million square feet. Another major advantage in an SPF roof system, that
does not exist with any other roofing system, is that SPF is a renewable system.
While BURs and singly-plys must be removed and replaced after their usable lives,
SPF roofs can be repaired and recoated to offer an indefinite life expectancy.
Coupled with the energy savings and reduction in in-house maintenance costs,
the SPF roofing system maintains a tremendous long-term cost efficiency advantage
over all other roofing systems. Without question SPF roofs have a tremendous
edge in preventing leaks and in detection and repair when one does occur. The
conclusion of today's Physical Plant Department has not varied from the conclusion
reached by Gerald Scott in 1985. We at the Physical Plant Department continue
to monitor the progress of other roofing systems available. But at this time,
no other roofing system can offer the leak free service, the ease of leak detection
and maintenance, the energy efficiency, durability, or renewability provided
by sprayed polyurethane foam roofs.